CCTV power backup: how installers size a UPS for cameras and recorders
CamVerion team · 19 November 2026 · 7 min read
Quick answer
Back up the recorder, PoE switches and router, then size the UPS from their total watts and the runtime the customer needs, with headroom. Add surge protection on outdoor runs, plan for battery replacement every three to five years, and quote backup as a clear option rather than leaving it out.
A CCTV system that stops recording when the power goes off has a serious weakness. Power cuts are common in many areas, and some intruders cut power on purpose. Even short outages can corrupt recordings, damage hard drives and leave cameras offline until someone resets them.
Power backup is often left off quotes to keep the price down. That is a mistake for most commercial jobs, and for many homes too. This guide covers how to plan backup power properly and explain it to customers.
What needs backup power
In a typical IP system, the parts that need power are:
- The recorder (NVR or DVR).
- The PoE switch, which powers the cameras.
- Cameras with separate power supplies, if they are not PoE.
- The internet router or modem, if remote viewing and alerts are needed during an outage.
- Monitors, if live viewing is needed during an outage. Often these can be left off backup to save capacity.
In a PoE system, putting the recorder and PoE switch on a UPS keeps every camera running. This is one of the big advantages of PoE. In analogue systems with separate camera power supplies, the camera power supply also needs backup.
Types of backup
Offline (standby) UPS
The simplest and cheapest type. Equipment runs from mains until the power fails, then the UPS switches to battery. Fine for small systems, although the brief switchover can occasionally cause sensitive equipment to restart.
Line-interactive UPS
Adds voltage regulation, which helps where mains voltage fluctuates. A good choice for most small and medium CCTV systems.
Online (double-conversion) UPS
Equipment always runs from the inverter, so there is no switchover at all. More expensive, but the best protection for critical systems and areas with poor power quality.
Inverters and home power backup
In many homes and small businesses, especially in India, a building already has an inverter with batteries. Connecting the CCTV system to the inverter circuit can be an economical solution. Check the switchover time, the inverter's capacity and whether it is already heavily loaded.
Battery-backed camera power supplies
For analogue systems, a power supply with a built-in battery can keep cameras running. Size it for the cameras' total current draw.
Sizing a UPS
Sizing has two parts: the load, and the runtime.
Step 1: Add up the load
List every device on the UPS and its power consumption in watts. Use the manufacturer's maximum figures, not the typical ones.
| Device | Example consumption |
|---|---|
| 8-channel NVR with one drive | 15 W |
| 8-port PoE switch with 8 cameras at 6 W | 60 W including switch overhead |
| Router | 10 W |
| Total | 85 W |
These are examples only. Use the datasheets for the actual equipment. Remember that cameras with infrared draw more at night, and PTZ cameras draw much more when moving or heating.
Our guide on PoE switch power budgets explains how to calculate camera loads.
Step 2: Choose a UPS with headroom
UPS ratings are given in VA and watts. Choose a UPS whose watt rating is comfortably above your load. A common rule of thumb is to keep the load below about 60% to 70% of the UPS's watt rating. This leaves room for growth and avoids running the UPS at its limit.
Step 3: Work out the runtime
Runtime depends on the battery capacity and the load. Manufacturers publish runtime charts showing how long a UPS will run at different loads. Use those charts rather than general formulas. If the required runtime is long, look for UPS models that accept external battery packs.
How much runtime does the customer need?
Ask the customer:
- How often does the power go off, and for how long?
- Is there a generator? How long does it take to start?
- Is it important to record during long outages, or only to ride through short cuts and shut down cleanly?
Typical needs:
| Situation | Typical runtime target |
|---|---|
| Site with a generator | Enough to cover generator start, often 10 to 15 minutes |
| Short, occasional cuts | 30 minutes to 1 hour |
| Frequent long cuts | Several hours, usually with external batteries or an inverter |
| Critical security sites | As long as the customer's risk assessment requires |
Clean shutdown
When the battery runs low, the recorder should shut down cleanly to protect the drive. Some UPS units can signal a connected device to shut down. Where the recorder doesn't support this, set the runtime target so the battery rarely runs out, or advise the customer that recording will stop once the battery is empty.
Surge protection
Power surges, often from lightning or switching, can damage recorders, switches and cameras. A UPS gives some protection on the mains side. For outdoor cameras, especially on long cable runs or tall poles, consider surge protectors on the network and power lines, and make sure equipment is properly earthed.
Installation tips
- Put the UPS near the recorder and switch, in a ventilated space.
- Label the UPS and the circuit, so nobody unplugs it to charge a phone.
- Don't plug heaters, kettles or printers into the UPS. They overload it.
- Test it at handover. Switch off the mains and check that everything keeps running, including remote viewing if the router is on backup.
- Record the UPS model and installation date in the job notes.
Battery care and replacement
UPS batteries wear out. Sealed lead-acid batteries in many small UPS units typically need replacing every few years, and sooner in hot environments. Signs of an ageing battery include shorter runtime, UPS warnings and the UPS failing a self-test.
Build battery checks into your maintenance visits. Our AMC guide explains how to include them in a maintenance contract. Planned battery replacement is a useful source of recurring revenue and prevents surprises.
Explaining backup to customers
Customers often see backup as an optional extra. Explain it in terms of risk:
"If the power goes off, the cameras stop recording. Some burglars cut the power before they break in. A backup unit keeps the cameras running for about an hour, and protects the recorder from damage."
Offer it as a clear line on the quote, with the runtime stated. If the customer declines, note it in the job record. Our quotation format guide shows how to present options clearly.
Quoting backup as an option
Customers rarely ask for backup power, so it is often left off the quote and becomes an argument after the first power cut. Offering it as a clearly priced option lets the customer decide and protects you later.
Contractor quotation software makes options easy. In CamVerion, keep a UPS package as a saved item or template line, add it to the quote with its runtime, and send the PDF the same day. Battery replacements can then be scheduled as part of a maintenance contract.
Common mistakes
- Leaving backup off commercial quotes to win on price.
- Backing up the recorder but not the PoE switch, so the cameras still go dark.
- Forgetting the router, so no alerts are sent during an outage.
- Sizing from typical, not maximum, power figures.
- Ignoring night-time infrared load.
- Never replacing batteries.
A quick checklist
- List every device that needs backup, including the switch and router.
- Add up maximum power consumption.
- Choose a UPS with 30% to 40% headroom.
- Use the manufacturer's runtime charts to meet the customer's needs.
- Add surge protection for exposed outdoor equipment.
- Label the UPS and keep other loads off it.
- Test it at handover by switching off the mains.
- Check and replace batteries as part of maintenance.
Power backup is a small part of the price and a big part of the reliability. When the lights go out, the customer will be glad the cameras didn't.
Frequently asked questions
What size UPS do I need for CCTV?
Add up the watts of the recorder, PoE switch with its cameras, and router, then choose a UPS whose battery gives the runtime needed at that load, with around 25 per cent headroom.
How long should CCTV run on backup power?
It depends on the customer: 30 minutes covers short cuts, while sites with long outages may need several hours or a generator.
How often should UPS batteries be replaced?
Every three to five years, sooner in hot rooms. Test them on maintenance visits by switching off the supply.